PID tuning

Make the loop behave.

P/I/D terms, tuning methods, symptoms, and implementation.

controlP I DZieglerwindup

A PID controller steers a process to its setpoint by combining three views of the error — present, past, and future. Tune the three gains and the loop settles fast, tracks accurately, and shrugs off disturbance.

Quick reference

The whole loop on one screen: the equation, the three terms, the tuning order, and the constants you’ll actually reach for.

1. The equation

Output = present + past + future.

u = Kp·e + Ki·∫e dt + Kd·de/dt

2. P — proportional

Acts on error e = r − y now. Raise for speed; too high → overshoot + oscillation.

3. I — integral

Sums past error ∫e dt. Kills steady-state offset; too high → slow oscillation + windup.

4. D — derivative

Rate of change de/dt. Damps overshoot; too high → noise, jittery output.

5. Tune in order

P first, then D, then I — one gain at a time, watch the step after each move.

6. Ziegler–Nichols

Ultimate gain: Kp = 0.6·Ku, Ti = Tu/2, Td = Tu/8. Aggressive — back off 20–30%.

7. Anti-windup

Clamp u and stop integrating while saturated, or the integral overshoots on recovery.

8. Derivative on measurement

Differentiate y, not e — avoids a derivative kick on setpoint steps.

The PID loop

A PID controller closes a feedback loop: measure, compare to the setpoint, compute a correction, apply it, repeat.

Setpoint (r — target) → Error (e = r − y) → PID (Kp·e + Ki·∫e + Kd·de/dt) → Plant (process) → Output (y — measured)

1. Setpoint

The target r the process should hold — a temperature, speed, level, or position.

2. Error

The gap the controller acts on: e = r − y. Zero error means the loop is on target.

3. Output

The control signal u sent to the actuator — heater power, valve position, motor PWM.

4. Feedback

The measured y loops back and is subtracted from r to recompute e every sample.

KEY: The loop closes when the measured output y is subtracted from the setpoint r to form the error e — the only signal the controller sees. Each sample, the PID computes u from e and writes it to the actuator; the plant responds; the sensor reads the new y; the cycle repeats.

Worked example: one sample

Setpoint r = 100, measurement y = 90, gains Kp = 2, Ki = 0.5, Kd = 1, dt = 0.1, integral so far 2, previous measurement 88.

e        = 100 - 90        = 10
P term   = 2 * 10           = 20
integral = 2 + 10 * 0.1     = 3
I term   = 0.5 * 3          = 1.5
D term   = 1 * (88 - 90)/0.1 = -20
u        = 20 + 1.5 - 20    = 1.5

One sample, three terms: P pushes on the present error, I adds the accumulated history, D pulls back because the measurement is rising toward the setpoint.

P, I, D terms

Proportional (now), integral (past / steady-state), derivative (future / damping) — what each fixes and what it breaks.

TermLooks atWhat it fixesWhat it breaks
P proportionalpresent error espeeds response, reduces error nowtoo high → overshoot + oscillation; leaves steady-state error
I integralaccumulated past error ∫e dteliminates steady-state errortoo high → slow oscillation + windup
D derivativerate of change de/dtdamps, predicts, reduces overshoottoo high → amplifies noise, jittery output

Now, past, future

P answers the present, I remembers the past, D anticipates the future. Most loops get P first, then D, then I — in that order.

error   = setpoint - measurement
output  = Kp*error
output += Ki*integral_of(error)
output += Kd*derivative_of(error)

Parallel vs ideal form

Parallel form uses Ki and Kd directly. Classic tables give integral time Ti and derivative time Td instead — convert with Ki = Kp/Ti and Kd = Kp·Td.

u = Kp·e + (Kp/Ti)·∫e dt + (Kp·Td)·de/dt
Ti = Kp/Ki      Td = Kd/Kp

Raise / lower

  • Kp ↑ — faster, more overshoot.
  • Kp ↓ — slower, steadier.
  • Ki ↑ — kills offset, more windup risk.
  • Kd ↑ — more damping, more noise.

Symptoms

Read the step response: the shape of the curve tells you which gain to move.

SymptomLikely causeAdjust
Overshoot on a stepKp too high, or Kd too lowlower Kp or raise Kd
Sustained oscillationKp (or Ki) too highlower Kp, then Ki
Slow / sluggish responseKp too lowraise Kp
Steady-state error (offset)Ki missing or too lowraise Ki
Noisy / jittery outputKd too highlower Kd or filter the derivative
Slow settle after oscillationKd too lowraise Kd

⚠: Change one gain at a time and watch the step response after each move. If you touch two knobs at once you can’t tell which one helped.

What the curve looks like

Four classic step-response shapes and their diagnosis:

overdamped   — slow rise, no overshoot   →  raise Kp
underdamped  — fast rise, rings a bit    →  raise Kd
critically   — fast rise, no overshoot   →  just right
oscillating  — never settles             →  lower Kp, then Ki

Tuning methods

Manual, Ziegler-Nichols, Cohen-Coon, trial and error, and software autotune.

Manual (by feel)

Raise Kp until the loop oscillates, then halve it. Add Kd to damp, then a little Ki to remove the remaining offset.

Trial & error (P → D → I)

Fix one gain at a time, in order: P for speed, D for damping, I for accuracy. Watch the step response after each move.

Software autotune

Relay/step injection built into motor drives, PLCs, and 3D-printer firmware (Marlin, Klipper) excites the loop and fits gains automatically.

MethodKpTi (integral time)Td (derivative time)
Ziegler–Nichols — ultimate gain0.6·KuTu / 2Tu / 8
Ziegler–Nichols — reaction curve1.2·T/(K·L)2·L0.5·L
Cohen–Coon(T/(K·L))·(4/3 + L/(4T))L·(32 + 6·L/T)/(13 + 8·L/T)4·L/(11 + 2·L/T)

⌁: Reading the table: Ku is the ultimate gain (the Kp that just sustains oscillation) and Tu is that oscillation’s period. Reaction-curve methods use the open-loop step response: K = process gain, L = dead time, T = time constant. Convert times to parallel gains with Ki = Kp/Ti and Kd = Kp·Td. Ziegler–Nichols targets ~25% overshoot (quarter-amplitude decay) and is aggressive on real plants — back Kp off 20–30% before commissioning.

Ziegler–Nichols: finding Ku and Tu
  1. Zero I and D — Set Ki = 0 and Kd = 0 so only P acts.
  2. Raise Kp to the edge — Increase Kp until the output oscillates with a constant amplitude.
  3. Record Ku — That edge gain is the ultimate gain Ku.
  4. Measure Tu — Time one full oscillation — that period is Tu.
  5. Apply the tableKp = 0.6·Ku, Ti = Tu/2, Td = Tu/8. Back Kp off 20–30% to soften the response.
Reading the reaction curve (K, L, T)

Step the output by Δu with the loop open and record the response, then read three numbers:

K = Δy / Δu         process gain
L = dead time       before y starts moving
T = time constant   y reaches ~63% of its final change

Feed K, L, and T into the Ziegler–Nichols or Cohen–Coon row above.

Practical tuning

Start P only, add D, add I last. Watch the step response, limit the output, and differentiate the measurement.

  1. Zero I and D — Set Ki = 0 and Kd = 0. Start with a small, safe Kp.
  2. Raise P — Increase Kp until the step response is reasonably fast — stop before it oscillates.
  3. Add D to damp — Increase Kd to cut overshoot and settle the oscillation.
  4. Add I last — Raise Ki a little to remove steady-state offset.
  5. Clamp & verify — Clamp u to the actuator limits and repeat a step to confirm the response.

Read the step response

Apply a small setpoint step and watch rise time, overshoot, and settle time. The shape tells you which gain to move — see the symptom table above.

rise time  →  dominated by Kp
overshoot  →  Kp too high / Kd too low
offset     →  Ki too low (or zero)
ringing    →  Kd too low, or Kp too high

Derivative on measurement

Compute the derivative from the measurement y, not the error e, so a setpoint step doesn’t inject a derivative spike.

// on measurement (preferred):
d_term = kd * (prev_measurement - measurement) / dt;
Cheat-map: symptom → action
  • overshoot — lower Kp or raise Kd.
  • oscillation — lower Kp, then Ki.
  • too slow — raise Kp.
  • offset — raise Ki.
  • noisy output — lower Kd or filter the derivative.
  • slow settle — raise Kd.

Integral windup & filters

Anti-windup, derivative on measurement (not error), and noise filtering keep a tuned loop honest.

Integral windup

When the output saturates, the integral keeps accumulating and overshoots on recovery. Clamp it (or stop integrating) while saturated.

Derivative on measurement

Differentiating the error couples the derivative to setpoint jumps. Differentiate the measurement instead — the process moves smoothly.

Noise filtering

Differentiation amplifies sensor noise. Low-pass filter the derivative (or the measurement) before it reaches the D term.

Anti-windup + filtered derivative, in one pass

// anti-windup: stop integrating in the direction of saturation
if (out >= out_max && error > 0.0f) integral -= error * dt;
if (out <= out_min && error < 0.0f) integral -= error * dt;

// derivative on measurement (not error): no setpoint kick
d_term = kd * (prev_measurement - measurement) / dt;

// optional: low-pass the derivative to kill noise
d_term = 0.8f * d_term + 0.2f * d_term_prev;

Implementation

A discrete-time PID skeleton in C: the equation, dt, output clamping, and derivative on measurement.

The state

Keep gains, the integral, the previous measurement, the sample time dt, and output clamps in a struct.

typedef struct {
  float kp, ki, kd;        // gains
  float integral;          // ∫ e dt
  float prev_measurement;  // for derivative
  float dt;                // sample time (s)
  float out_min, out_max;  // output clamps
} PID;

The update

Compute P, I, D in discrete time, combine, clamp, and return. Call once per sample period.

float pid_update(PID *p, float setpoint, float measurement) {
  float error = setpoint - measurement;

  // proportional — the present
  float p_term = p->kp * error;

  // integral — the past
  p->integral += error * p->dt;
  float i_term = p->ki * p->integral;

  // derivative on measurement — the future
  float d_term = p->kd *
    (p->prev_measurement - measurement) / p->dt;
  p->prev_measurement = measurement;

  // combine and clamp the output
  float out = p_term + i_term + d_term;
  if (out > p->out_max) out = p->out_max;
  if (out < p->out_min) out = p->out_min;
  return out;
}

✓: dt is a gain. Because I and D scale with sample time, use a fixed dt (or measure the real elapsed time each call) and re-tune if it changes. The clamp keeps the actuator inside its physical range and is a first line of defense against windup.

Discrete difference equation

The continuous form is discretized with a fixed sample time dt:

e[k]          = setpoint - measurement
integral[k]   = integral[k-1] + e[k] * dt
derivative[k] = (prev_measurement - measurement) / dt

u[k] = Kp*e[k] + Ki*integral[k] + Kd*derivative[k]

Initialize prev_measurement = measurement on the first call so the derivative term starts at zero instead of spiking.

Pitfalls

Too much D, windup, wrong sign, dt drift, deadband — and the subtler ones: stiction, nonlinear plants, and noisy measurements.

Too much D amplifies noise

Derivative gain multiplies sensor noise and high-frequency jitter. If the output chatters, lower Kd or low-pass the derivative term.

Integral windup

Once the actuator saturates, the integral keeps growing, so the loop overshoots on recovery. Clamp the integral or stop integrating while saturated.

Wrong sign

A reversed polarity (positive instead of negative feedback) makes the loop run away. Check that increasing u drives y toward r, not away.

dt inconsistency

If the sample period changes between tuning and running, I and D change too. Use a fixed dt or measure elapsed time every call.

Deadband too wide

A deadband that turns the output off near zero error can produce a small limit cycle — the loop hunts around the setpoint instead of settling.

Stiction & backlash

A valve or linkage that sticks ignores small corrections, so the loop overshoots once it finally breaks free. Add a small deadband, dither, or a positioner.

Nonlinear plant

Gains tuned at one operating point can oscillate at another. Tune near the real setpoint, or schedule gains across the range.

Noisy measurement

A noisy sensor pollutes D however low Kd is. Low-pass the measurement (or derivative) first, then bring D back.

⚠: Before tuning, prove the feedback is stable: nudge the output by hand and confirm the measurement moves the way you expect. A wrong sign or a dead sensor makes any tuning session futile.